4.3 Enable Supervision of Wireless Zones
NOTE (for PC5010 v1.x control panels only): In order for wireless zones to be
supervised, you must enable Double End of Line supervision in the PC5010
control panel. For more information, refer to your PC5010 v1.x Installation
Manual.
NOTE (PC5010 v2.0 and higher, PC1555, PC580 only): For wireless supervi-
sion to work, you must enable the wireless zone attribute on all wireless zones
(sections [101] to [132], option [8] ON).
Wireless Supervisory Window
Each wireless zone (WLS904, WLS906, WLS906, or WLS907) will send a
supervisory signal every 12 minutes. If the receiver does not receive a signal
within the time programmed for the Wireless Supervisory Window, it will
generate a supervisory fault.
To program the wireless supervisory window:
1. Enter [✱][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132-RS Module Programming.
3. Enter sections [81].
4. Enter the time period for the supervisory window (valid entries are 01-24
hours).
5. To exit press [#].
WLS908 Panic Pendant
The panic pendant does not transmit a supervisory signal. This is so that the
user will be able to take it away from the premise. You must disable wireless
supervision for each zone a panic pendant is assigned to.
Disable/Enable Zone Supervision
All wireless zones have supervision enabled by default. To disable supervision
for any zone, enter the following at any system keypad:
1. Enter [✱][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132-RS Module Programming.
3. Enter sections [82], [83], [84] and [85]. Disable or enable supervision for
each wireless zone by turning each relevant option on or off.
4. To exit press [#].