Specifications
G E T T I N G S T A R T E D
6
End of Line Resistors ................................. Section [013]: [1]
Single End of Line Resistors ...................... Section [013]: [2]
Double End of Line (DEOL) Resistors
If the Double EOL option is enabled, all hardwire
zones must also be wired for Double EOL resis-
tors.
Double End of Line resistors allow the panel to determine if the
zone is in alarm, tampered or faulted.
To enable double end of line resistors, programming section
[013], option [1] must be OFF and option [2] must be ON (see
Section 4 “How to Program”).
This option can only be selected if Normally
Closed (NC) detection devices or contacts are
being used
(ie: Do not use DEOL resistors for Fire
zones or LINKS Supervisory zones).
Only one NC contact can be connected to each
zone. Wiring multiple detection devices or
contacts on a single loop is not allowed
.
Keypad zones do not support DEOL resistors.
The following chart shows zone status under certain conditions:
Loop Resistance Loop Status
0Ω (shorted wire, loop shorted) Fault
5600Ω (contact closed) Secure
Infinite (broken wire, loop open) Tamper
11200Ω (contact open) Violated
End of Line Resistors ................................. Section [013]: [1]
Double End of Line Resistors .................... Section [013]: [2]
2.9 Fire Zone Wiring
2-Wire Smoke Detectors
The following 2-wire smoke detectors may be used: ESL429AT
and DSC MN220. If PGM2 has been programmed for a 2-wire
Smoke Detector connection
,
the detectors must be wired
according to the following diagram:
If PGM2 is programmed for 2-wire smoke support,
the connector JP1 on the main board must be
removed.
4-Wire Smoke Detectors
All fire zones must be wired according to the following diagram:
2.10 24-Hr Auxiliary Input Wiring (PGM2)
If PGM2 has been programmed for 24-hour operation, the zone
must be wired according to the following diagram:
If PGM2 is programmed for 24-hour operation, the
connector JP1 on the main board must be removed.
2.11 LINKS Zone Wiring
LINKS Support
When using the LINKS 1000 cellular communicator, the
connection must be made according to the accompanying
diagram.
LINKS Supervisory
When using the LINKS 1000 cellular communicator, any main
board zone may be configured for LINKS Supervisory.
With a LINKS Supervisory zone, if the LINKS 1000 experiences
a trouble, the zone will be violated, causing the panel to report
the event to the central station. This type of zone
always
requires a single EOL resistor (5600Ω).
The LINKS Supervisory zone must be wired according to the
accompanying diagram.










