Specifications

43
SIA Format
A P P E N D I X B
* Zone Number is Identified
User Number is Identified
Each Zone Number is Identified (using UB-XX)
SIA Format
Level 2 (Hardcoded)
The SIA communication format used in this product follows the level 2 specifications of the SIA Digital Communication Standard -
January 1996. This format will send the Account Code along with its data transmission. The transmission would look similar to the
following at the receiver:
N Ri01 BA 01
N = New Event
Ri01 = Partition /Area Identifier
BA = Burglary Alarm
01 = Zone 1
PC1555 Reporting Codes SIA Identifiers &
Auto-Reporting Code
Delay Zone Alarm/Restore ....................................... BA-XX / BH-XX *
Instant Zone Alarm/Restore ..................................... BA-XX / BH-XX *
Interior Zone Alarm/Restore..................................... BA-XX / BH-XX *
Delay S.A. Zone Alarm/Restore .............................. BA-XX / BH-XX *
Interior S.A. Zone Alarm/Restore ............................BA-XX / BH-XX *
24 Hr Burg Zone Alarm/Restore..............................BA-XX / BH-XX *
Standard Fire Zone Alarm/Restore ..........................FA-XX / FH-XX *
Delayed Fire Zone Alarm/Restore............................FA-XX / FH-XX *
24 Hr Supervisory Buzzer Zone Alarm/Restore ..... UA-XX/ UH-XX *
24 Hr Supervisory Zone Alarm/Restore ................. UA-XX / UH-XX *
24 Hr Medical Zone Alarm/Restore .......................MA-XX / MH-XX *
24 Hr Panic Zone Alarm/Restore ............................ PA-XX / PH-XX *
24 Hr Holdup Zone Alarm/Restore......................... HA-XX / HH-XX *
24 Hr Gas Zone Alarm/Restore .............................. GA-XX / GH-XX *
24 Hr Heat Zone Alarm/Restore..............................KA-XX / KH-XX *
24 Hr Emergency Zone Alarm/Restore.................. QA-XX / QH-XX *
24 Hr Sprinkler Zone Alarm/Restore ....................... SA-XX / SH-XX *
24 Hr Water Zone Alarm/Restore .......................... WA-XX / WH-XX *
24 Hr Freeze Zone Alarm/Restore .......................... ZA-XX / ZH-XX *
24 Hr Latching Tamper Alarm/Restore ...................BA-XX / BH-XX *
Duress Alarm .......................................................................... HA-00
Opening After Alarm............................................................... OR-00
Recent Closing........................................................................ CR-00
Zone Expander Supervisory Alarm/Restore ............. UA-00/UH-00
Keypad Fire Alarm/Restore ...................................... FA-00 / FH-00
Keypad Auxiliary Alarm/Restore ............................ MA-00 / MH-00
Keypad Panic Alarm/Restore ................................... PA-00 / PH-00
2-wire Smoke Alarm/Restore.................................... FA-99 / FH-99
Audible/Silent 24 Hr.................................................. UA-99 / UH-99
PC1555 Reporting Codes SIA Identifiers &
Auto-Reporting Code
Zone Tamper (1-8) ....................................................................TA-XX *
Zone Tamper Restorals (1-8) ...................................................TR-XX *
General System Tamper/Restore............................... TA-00 / TR-00
Keypad Lockout........................................................................ JA-00
Closing By Access Codes 1-32, 33, 34, 40-42...................... CL-XX
Partial Closing ..........................................................................CG-XX
Special Closing (DLS, Keys, Maint, Quick)............................. CL-00
Opening By Access Codes 1-32, 33, 34, 40-42 .................... OP-XX
Auto-Arm Cancellation..............................................................CE-00
Special Opening (DLS, Keys, Maint)...................................... OP-00
Battery Trouble Alarm/Restore .................................... YT-00/YR-00
AC Failure Trouble Alarm/Restore ..............................AT-00/AR-00
Bell Circuit Trouble Alarm/Restore.............................. UT-99/UJ-99
Fire Trouble Alarm/Restore........................................... FT-00/FJ-00
Auxiliary Power Supply Trouble Alarm/Restore ........ YP-00/ YQ-00
TLM Trouble Code (via LINKS) ................................................ LT-00
General System Trouble/Restore................................ YX-00/YZ-00
General System Supervisory/Restore......................... ET-00/ER-00
TLM Restoral ............................................................................. LR-00
FTC Restoral .............................................................................YK-00
Event Buffer 75% Full Since Last Upload ................................JL-00
DLS Lead In ..............................................................................RB-00
DLS Lead Out (Successful)......................................................RS-00
Periodic Test Transmission ......................................................RP-00
System Test...............................................................................RX-00
LINKS1000 Test Transmission Code....................................... TX-00
General Transmitter Low Battery/Restore .................. XT-00/XR-00
General Zone Trouble/Restore .................................... UT-00/UJ-00
Cross Zone Police Code ..........................................................BV-00
Delinquency Code ................................................................... CD-00
NOTE: Activity Delinquency will transmit the identifier for
Closing Delinquency (CD-00).