Specification

DryConn
®
DB Power Connect
MADE IN USA
50100-79 REV A 07/13
PRODUCT DATA AND TESTING INFORMATION:
Immersion Sequence:
- Immersion - 24 hours in 1 foot head of water
- Dielectric Withstand - 2200Vac for 1 minute
- Insulation Resistance - 500Vdc for 1 minute
- Oven Aging - 50°C for 72 hours
- Flex & Twist - 10 side to side flexes & 5 30° twists
- Immersion - 24 hours in 1 foot head of water
- Insulation Resistance - 500Vdc for 1 minute
- Cold Conditioning - –18°C for 4 hours
- Flex & Twist - 10 side to side flexes & 5 30° twists
- Immersion - 24 hours in 1 foot head of water
- Insulation Resistance - 500Vdc for 1 minute
- Dunk Test - 1 hour at 125A for #4 or30A for #14 followed by 30 minutes
immersed in 1 foot head of water. Repeat for 25 cycles
- Dielectric Withstand - 2200Vac for 1 minute
- Insulation Resistance - 500Vdc for 1 minute
Oven Aging Sequence:
- Immersion - 1 hour in 1 foot head of water
- Dielectric Withstand - 2200Vac for 1 minute
- Insulation Resistance - 500Vdc for 1 minute
- Oven Aging - 90°C for 72 hours
- Flex & Twist - 10 side to side flexes & 5 30° twists
- Immersion - 24 hours in 1 foot head of water
- Dielectric Withstand - 2200Vac for 1 minute
- Insulation Resistance - 500Vdc for 1 minute
Impact Sequence (Cold Conditioned and As Received):
- Cold Conditioning - –10°C for 2 hours
- Impact - Samples impacted with a 1.18 lbs, 2” diameter steel sphere dropped from 36”
- Immersion - 4 hours in 1 foot head of water
- Dielectric Withstand - 2200Vac for 1 minute
Submersion Sequence:
- Submersed - 30 minutes in 6 foot head of water
- Dielectric Withstand - 2200Vac for 1 minute
Note:
The above test sequences were conducted on separate sample sets.
Conductor combinations tested:
(3) #4 conductors
(2) #14 conductors