Specifications
Rocket Installation and Operation Manual     
31 
7.3  Floor protector 
If the stove is to be installed on top of a combustible floor, it must be guarded by a non 
combustible material as shown on figure 1.3 (see the dotted line area). 
FLOOR PROTECTOR* 
CANADA USA 
G 
8’’ (203 mm) – Note 1  N/A (Canada only) 
H 
8’’ (203 mm)  N/A (Canada only) 
I 
18’’ (457 mm) 
From door opening 
16’’ (406 mm) 
From door opening 
J 
N/A (USA only)  8’’ (203 mm) 
M 
8’’ (203 mm)  N/A (Canada only) 
N 
N/A (USA only)  Note 2 
*Steel with a minimum thickness of 0.015’’ (0.38 mm) or ceramic tiles sealed together 
with grout. No protection is required if the unit is installed on a non-combustible floor 
(ex: concrete). 
Note 1: The floor protection at the back of the stove is limited to the stove’s required 
clearance if such clearance is smaller than 8 inches (203 mm). 
Note 2: Only required under the horizontal section of the connector. Must exceed each 
side of the connector by at least 2 inches (51 mm). 
7.4  Reducing Wall and Ceiling Clearances Safely 
It is often desirable to reduce the 
minimum installation clearances 
by placing the stove closer to 
walls so the installation takes up 
less floor space. You can safely 
reduce the minimum clearances 
by permanently installing a shield 
between the stove and 
combustible material. The rules 
for safe shields can be 
complicated, so read them 
carefully and follow them exactly. 
Note that there may be minor 
regional differences in clearance 
reduction rules so be sure to 
check with your building or fire 
inspector before proceeding. 










