Installation Guide
Page 8 INSTALLATION MANUAL ECO-55 / ECO-55 CT / ECO-55 ST
ENGLISH
3.2 FLOOR PROTECTION
MINIMUM CLEARANCES
CANADA USA
C
3" (76 mm) 3" (76 mm)
D
Note 1 Note 1
RECOMMENDED CLEARANCES FOR
MAINTENANCE
CANADA USA
C
12" (305 mm) 12" (305 mm)
D
Note 1 Note 1
Note 1 : Refer to the exhaust venting system manufacturer’s
instructions for clearances to combustible materials.
FLOOR PROTECTION
CANADA** USA
E
6" (152 mm)
From door opening
6" (152 mm)
From door opening
F
6" (152 mm)
From door opening
6" (152 mm)
From door opening
CAUTION
THE STOVE MUST BE PLACED ON
A CONTINUOUS (GROUTED JOINTS)
NONCOMBUSTIBLE MATERIAL SUCH AS
CERAMIC TILE*, CEMENT BOARD, BRICK,
MILLBOARD OR EQUIVALENT, OR ANY OTHER
APPROVED OR LISTED MATERIAL SUITED
FOR FLOOR PROTECTION.
*Any type of tile will require a continuous non combustible sheet
beneath to prevent the possibility of embers falling through to the
combustible oor if cracks or separation should occur in the ni-
shed surface, this would include oor protection for built-in raised
hearths. Check local codes for approved alternatives.
**You may reduce the oor protection requirements to the values
shown in the previous table ONLY if the following actions are
respected: Allow for the appliance to shut-down and re to
be extinguished. Once completely cool and all blowers have
stopped you may proceed with opening the rebox or ash door.
Otherwise, see CSA B365.