Product Manual
Eco-65 Installation and Operation Manual
65
filled the tube around the igniter. Refer to
Section 7: Maintenance. Also, make sure
that recommended fuel is used (see Section
4.8.1: Proper Fuel) and settings are adjusted
to the type of pellets that are being used
4. Air intake channel is restricted. Visually inspect the air intake channel that
leads to the burn pot for foreign material.
Make sure that the air-intake shutter is
functional and free of any obstruction.
5. The combustion/exhaust blower failed. See Section 8.2: Testing a Component and
test the combustion and the exhaust blowers
independently. If one of them does not
function, make sure there is power and that
the blowers are properly connected. If they
still don’t work, check fuse F4 and F5 on the
control board. A blown fuse will be darkened
or will have a broken filament. If the fuses are
in good condition, the combustion or exhaust
blower is probably defective. Replace the
faulty part.
8.3.13 No Display
• The control board does not display any information.
Possible Cause: Possible Remedy :
1. There is no electrical current going to the
stove.
Check if the stove is connected and if there is
current in the wall outlet. Check if the F7 fuse
is blown. Replace it if necessary.
2. TELCO wire is defective or not connected
properly.
Convection blower, combustion blower,
exhaust blower and burn pot auger will start
but the stove will beep continuously. Verify
the connection between the control panel and
the electronic card. Change wire if necessary.