HeatPack Furnace Installation and Operation Manual
19
7.1.2 Adjustable height of the plenum; (with the plenum extension cut off A).
When the ceiling height, measured from
the floor is greater than 72" (183 cm),
but less than 84" (213 cm), it will be
possible to cut the plenum extension (A)
of at most 10" (254 mm). The plenum
extension (A) must therefore have a
minimum height of 14" (356 mm)
Warning: The plenum extension (A)
should not obstruct the openings for the
hot air distribution of the plenum (B).
The shaded area represents the
maximum cutting of plenum extension
(A).
7.1.3 Adjustable height of the plenum (A and B)
For ceiling height greater than 84"
(213 cm), use plenum extension (A)
without cut off and plenum (B).