Maximum unsupported horizontal length: 3 feet (1 m);
Galvanized flue pipes must not be used because the coating vaporize at high
temperatures and release dangerous gases;
Flue pipes must be at least 24 gauge in thickness;
The chimney connector must be in good condition;
Flue pipe joints should overlap 1 1/4". (30 mm);
It should not be necessary to move the furnace to maintain the exhaust system.
The male ends of the pipe sections must be oriented towards the appliance so that
falling dust and condensation stay inside the pipe;
The use of 45° elbows is strongly recommended;
Never use more than two 90° elbows.
Use 45° elbows where possible, rather than 90° elbows.
Alternative installations with 90° elbow or tee.