Specifications
Installing the control panels
2.1.2
Thermal design of the enclosures
2
-4
Internal temperature rise of a panel with an internal fan
The size of the enclosure is assumed 450 (W) × 790 (H) × 150 (D) mm.
The calculated internal temperature rise ΔT = 9.8 ( ℃ ), thus the temperature rise require-
ment of 10 ℃ is satisfied.
If the temperature rise requirement is not satisfied, additional measure must be taken to
lower the temperature rise.
Capacity of heat exchangers
If an internal fan alone is not sufficient for satisfying the temperature rise requirement, a
heat exchanger must be installed (see the table below).
Table 2.2 Heat exchanger
Note: Capacity means the amount of heat that a heat exchanger can remove,
on the ground that the temperature rise must be kept 10
℃
or less.
Maximum internal heat that can be safely produced in a panel
equipped with a heat exchanger
Up to 359 W of internal heat can be safely produced in a panel if it is equipped with a heat
exchanger of table 2.2, as shown below.
• P
=
k
・
A
・△
T
+
110W/10
℃=
6
×
4.16
×
10
+
110
=
359W/10
℃
• Effective surface area
A = 1.0155 (m
2
)
(the bottom surface is excluded as the panel is of stand-alone type)
• Internal heat produced P = 60 (W)
• Internal temperature rise
Type Designation Capacity Outside dimensions (mm)
DE9404550-1 REX1600ESYE
110W/10
℃
194 : (W) 800 : (H) 65 : (D)
EXAMPLE
450mm
150mm
790mm
△
T
=
P
qe
P
k
・
A
==
60
6
×
1.0155
=
9.8 (℃)
EXAMPLE