Specifications
14.1
Fundamental settings
14
-31
14.1.8 Various mask settings
Settings at CNC
At CNC, you can mask some processing to be done with each drive. Always set the parame-
ter to "0" to disable the masks unless you specifically need to use the masks for temporary
examination purpose or so.
• MD13070 DRIVE_FUNCTION_MASK [0] (1st axis) ##
MD13070 DRIVE_FUNCTION_MASK [1] (2nd axis) ##
: (Repeat for all remaining axes)
Meaning: d0 --- Reading alarm from a drive
d1 --- Reading ACC file (parameter definition file) from a drive
d2 --- Reading encoder-related parameters from a drive
d3 --- Reading drive control-related parameters from a drive
Setting value: 0 --- Not to be masked
1 --- To be masked
Standard setting value: 0
Settings at drive
Spindle drive
By setting this parameter, you can mask the following alarms.
• MD7018 (Cn8E6) ALARM_MASK (For each axis)
Meaning: Alarm mask
Initial value: 0000 (Hex)
The following shows alarms to be masked with bit wise settings:
d0: ALM_OHL Motor thermistor wire break (A:79)
d1: ALM_OHM Motor overheat 2 (A:79)
d2: ALM_CUV Control circuit low voltage (A:43)
d3: ALM_IFANERR Internal cooling fan error (A:75)
d4: ALM_OHF Heat sink overheat 2 (A:7A)
d5: ALM_UV Under voltage (A:41)
d6: ALM_ADE850E CPU-embedded A/D error (A:B2)
d7: ALM_WDC_ERR WDC error (A:E2)
ALM_DPRAM DPRAM error (A:06)
ALM_COMSYNC Network synchronization error (A:E5)
d8: ALM_FPGBREAK1 FPG wire break (PA and PB) (A:C6)
d9: ALM_FPGBREAK2 FPG wire break (PC) (A:C7)
d10: ALM_DEV Speed deviation too large (A:53)
Setting example: When Spindle motor is removed off --- 0303H (Set d0, d1, d8, and d9
to "1".) With this setting, Spindle servo can be turned on.