Specifications

12.2
Application
12
-29
6. Press the [DATA/ENTER] key to return to the auxiliary function execution mode dis-
play.
This completes the motor current detection signal offset automatic adjustment.
Motor current detection signal offset manual adjustment
Use the following procedure for the offset manual adjustment of motor current detection sig-
nal.
Before initiating the manual adjustment, run the motor at about 100 min
-1
and adjust the ripple for the
torque reference monitor (See the Section 16.4 "Analog monitor") becomes minimum. You must bal-
ance the U-phase and V-phase current offset when adjusting. For this purpose, you have to adjust alter-
nately these phase current offsets several times.
1. On the axis selection mode, select the axis you want to operate.
2. Press the [DSPL/SET] key to select the auxiliary function execution mode.
3. Select the user constant Fn00F. Press the [LEFT] or [RIGHT] key to select the setting
digit. Press the [UP] or [DOWN] key until the value you want to set is displayed.
4. Press the [DATA/ENTER] key. The indication will be displayed as below.
5. Press the [DSPL/SET] key to switch over the U-phase (Cu1_0) to and from V-phase
(Cu2_0) current detection signal offset adjustment mode.
6. Press the [LEFT] or [RIGHT] key to view the current detection data. Press the [LEFT]
or [RIGHT] key again to return to the display of Step 4 or Step 5.
IMPORTANT
[DSPL/SET] key
Changes alternately.
Changes alternately.
[LEFT] key
([RIGHT] key)
Data display