Specifications
How to use Digital Operation
12.2.7
Manual zero adjustment and gain adjustment for analogue monitor output
12
-26
Analog monitor output manual zero adjustment
Use the following procedure for the manual zero adjustment of analog monitor output.
1. On the axis selection mode, select the axis you want to operate.
2. Press the [DSPL/SET] key and select the auxiliary function execution mode.
3. Select the user constant Fn00C. Press the [LEFT] or [RIGHT] key to select the setting
digit. Press the [UP] or [DOWN] key until the value you want to set is displayed.
4. Press the [DATA/ENTER] key. The indication will display like below.
5. Press the [DSPL/SET] key to switch over the 2-channel monitor output.
6. Press the [LEFT] or [RIGHT] key to view the analog monitor output data. Press the
[LEFT] or [RIGHT] key again to return to the display of Step 4 or Step 5.
7. Press the [UP] or [DOWN] key to enable the analog monitor output zero adjustment.
8. After the zero adjustment for the two output channels, press the [DATA/ENTER] key.
The indication will return to the auxiliary function execution mode display.
This completes the analog monitor output manual zero adjustment.
[DSPL/SET] key
Changes alternately.
Data display
Changes alternately
[LEFT] key
([RIGHT] key)
Data display
Data setting changed.