Page 4 • DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Specifications, capacities and
weights
Table 4-1:
XT humidifier specifications
XT
model kW
Max. steam
capacity
Current draw (amps)
Shipping
weight
Max.
operating
weight
Single-phase Three-phase
lbs/hr kg/h 120V 208V 230V 240V 277V 480V 600V 208V 240V 400V 480V 600V lbs kg lbs kg
5 1.7 5 2.3 14.2 8.2 7.4 7.1 47.2 21.4 46.3 21.0
10 3.4 10 4.5 16.3 14.8 14.2 12.3 7.1 5.7 9.4 8.2 4.9 4.1 3.3 47.2 21.4 46.3 21.0
20 6.7 20 9.1 32.2 29.1 27.9 24.2 14.0 11.2 18.6 16.1 9.7 8.1 6.4 48.1 21.8 54.0 24.5
30 10.1 30 13.6 ——————28.0 24.3 14.6 12.1 9.7 62.2 28.2 87.5 39.7
50 16.8 50 22.7 ——————46.6 40.4 24.2 20.2 16.2 62.2 28.2 87.5 39.7
75 25.1 75 34.0 ——————36.2 30.2 24.2 75.2 34.1 124.3 56.4
100 33.5 100 45.4 ————————48.4 40.3 32.2 75.2 34.1 124.3 56.4
150 50.3 150 68.1 ————————72.6 60.5 48.4 129.2 58.6 242.9 110.2
200 67.0 200 90.8 ————————96.7 80.6 64.5 129.2 58.6 242.9 110.2
Note: For circuit protection requirements, see Table 5-1.