Specifications
Page 4 • DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Specifications, capacities and
weights
Table 4-1:
XT humidifier specifications
XT
model kW
Max. steam
capacity
Current draw (amps)
Shipping
weight
Max.
operating
weight
Single-phase Three-phase
lbs/hr kg/h 120V 208V 230V 240V 277V 480V 600V 208V 240V 400V 480V 600V lbs kg lbs kg
5 1.7 5 2.3 14.2 8.2 7.4 7.1 — — — — — — — — 47.2 21.4 46.3 21.0
10 3.4 10 4.5 — 16.3 14.8 14.2 12.3 7.1 5.7 9.4 8.2 4.9 4.1 3.3 47.2 21.4 46.3 21.0
20 6.7 20 9.1 — 32.2 29.1 27.9 24.2 14.0 11.2 18.6 16.1 9.7 8.1 6.4 48.1 21.8 54.0 24.5
30 10.1 30 13.6 — ——————28.0 24.3 14.6 12.1 9.7 62.2 28.2 87.5 39.7
50 16.8 50 22.7 — ——————46.6 40.4 24.2 20.2 16.2 62.2 28.2 87.5 39.7
75 25.1 75 34.0 — ————————36.2 30.2 24.2 75.2 34.1 124.3 56.4
100 33.5 100 45.4 — ————————48.4 40.3 32.2 75.2 34.1 124.3 56.4
150 50.3 150 68.1 — ————————72.6 60.5 48.4 129.2 58.6 242.9 110.2
200 67.0 200 90.8 — ————————96.7 80.6 64.5 129.2 58.6 242.9 110.2
Note: For circuit protection requirements, see Table 5-1.