Specifications

Page 48 • DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Start-up procedure
Operation
Safety functions
XT humidifiers are protected against
running dry — current does not flow if the
electrodes in the steam cylinder are not
submerged in water.
If the current rating exceeds 120% of nominal
current, the drain valve opens automatically. As
the water level drops, the current rating drops
back to the nominal value.
If the current rating exceeds 120% of the
nominal current after several drainage
operations, the humidifier shuts down
automatically.
Capacity limitation
XT humidifier capacity can be limited to a
user-specified maximum:
Using the keypad/display or Web interface, from
the Main menu, and select Tank Setup, then
select Capacity Adjustment for menu options.
After the system is installed and connected properly:
1. Verify that the humidifier, controls, piping, electrical
connections, steam supply, and dispersion units(s) are installed
according to the following:
Installation instructions in this manual
Vapor-logic4 Installation and Operation Manual
– Installation section
– Installation checklist
Ladder style wiring diagram (inside humidifier cabinet)
External connections wiring diagram (inside humidifier
cabinet)
All governing codes
2. Verify that all electrical connections are secure before applying
power.
3. Make sure all electrical covers are in place and secure. See
Warning at left.
4. Verify that the humidifier is mounted level and securely
supported before filling with water. See operating weights in
Table 4-1.
5. Verify that the humidifier is level front to back and side to side
after it is full of water.
6. Read the “Operation” section of the Vapor-logic4 Installation
and Operation Manual.
Note: During start-up, do not leave the humidifier unattended.
7. Perform all applicable “Start-up checklist” items. See Page 49.
8. Monitor humidifier operation through multiple fill cycles. The
humidifier operating status appears on the keypad/display.
9. Perform the cleaning procedure as follows:
a. Operate the humidifier long enough for steam to be
produced.
b. Drain the cylinder completely using the keypad/display:
– At the Main menu, select Tank Status, and press Enter.
– Select Mode Auto, and press Enter.
– Select Drain, and press Enter.
– Let the cylinder drain for 5 to 10 minutes until empty.
c. Restart the humidifier, and repeat Steps a and b.
WARNING
Electric shock hazard
Only qualified electrical personnel should
perform start-up procedure.
Contact with energized circuits can cause
property damage, severe personal injury
or death as a result of electrical shock or
fire.
Make sure that all electrical covers are
in place and secure before turning on
electrical power. These include the heater
terminal cover, electrical panel cover, and
subpanel access panels.
XT humidifier and XTSB doors have lift-off hinges
for easy removal of open doors. The doors are
captivated when closed but should be removed
when open. An upward bump could damage the
door if it jumps the hinges and falls.