Specifications
Page 34 • DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Dispersion: 
Rapid-sorb
Installation
Figure 34-1: 
Rapid-sorb in a horizontal airflow with header outside the duct
A
A
Header outside of duct, horizontal airflow
1.  Mark and cut holes in the ductwork for the dispersion tubes. Use 
the L-bracket as a template to mark the holes on the duct floor.
2.  Temporarily, loosely suspend or support the header below 
the final location. Vertical balance point of the dispersion 
tube length dictates where the header should be suspended or 
temporarily supported.
3.  Mount the dispersion tubes to the header with the slip coupling 
or hose cuff (provided).
•  When installing slip couplings for 1½" (DN40) dispersion 
tubes, take care not to shear the O-rings. 
•  Set the slip coupling on the header stub or dispersion tube so 
the O-ring is resting on the face of the tubing.
•  Rotate the slip coupling as you push it onto the tubing. 
•  The O-rings are lubricated at the factory. If additional 
lubrication is necessary, DO NOT use a petroleum-based 
lubricant.
XT humidifier
Duct
Secure and seal escutcheon plates
90° long sweep or two 
45° elbows
OM-7627
¾" (DN20) copper
6" (150 mm) recommended
Header pitch:  
1/8"/ft (1%) minimum
1" (25 mm) air gap
5" (125 mm) recommended
Condensate drain ¾" pipe 
thread (DN20) 
Support bracket 
(0.421" [11 mm] mounting holes at 
top, bottom, and end)
Airflow
L-bracket. Install with flange facing upstream direction of airflow. 
Drawing shows L-bracket correctly positioned for airflow.
Dispersion tube. Orient with 
tubelets perpendicular to airflow. 
Slip coupling or 
hose cuff
Pitch (see Note 1)
Notes:
1   Pitch steam hose, tubing, or pipe toward Rapid-sorb: 
– 2"/ft (15%) when using steam hose 
– 1/8"/ft (1%) when using tubing or pipe
2  Use DRI-STEEM’s hard pipe adapter kit to connect steam outlet to hard pipe. Use a hose clamp to 
connect steam outlet to steam hose. Use a hose cuff and clamps to connect steam outlet to tubing.
Open drain required:
Locate air gap only in spaces with adequate temperature and air 
movement to absorb flash steam; otherwise, condensation may 
form on nearby surfaces. Refer to governing codes for drain pipe 
size and maximum discharge water temperature.
Steam hose, tubing, or pipe 
(tubing or pipe must be 
grounded). Insulate tubing 
and hard pipe to reduce 
steam loss. Do not insulate 
steam hose. See Table 24-1 for 
maximum piping lengths.
OM-351-1
Dimension A:
• 3.25" (82.5 mm) for 1½" tubes
• 5" (127 mm) for 2" tubes
Dispersion tube escutcheon plates
Dashed lines indicate provided by installer.
mc_062810_0815-XT
See Note 2