Specifications
DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 33
Dispersion: 
Rapid-sorb
Installation
Table 33-2:
Rapid-sorb dispersion tube capacities
Tube capacity Tube diameter
lbs/hr kg/h inches DN
≤ 35 ≤ 16 1½ 40
36-70 17-32 2 50
mc_060210_0935
Table 33-3:
Rapid-sorb header capacities
Header capacity Header diameter
lbs/hr kg/h inches DN
≤ 250 ≤ 113 2 50
251-500 114-227 3 80
501-800 228-363 4 100
801-1300 364-591 5 125
1301-2100 592-955 6 150
mc_060210_0936
Pitch requirements
•  For Rapid-sorb with the header outside a 
horizontal-airflow duct, consider the following:
–  1½" (DN40) dispersion tubes: Use a fastener of sufficient 
length to accommodate the 1/8"/ft (1%) pitch requirements 
toward the ¾" pipe thread (DN20) header drain fitting.
–  2" (DN50) dispersion tubes: The bracket can be mounted 
flush to the ductwork. The 1/8"/ft (1%) pitch typically can be 
accomplished in the length of the hose cuffs used to connect 
the tubes to the header. 
•  See Table 33-1 and the drawings on the following pages for 
pitch requirements. 
mc_060210_0953-NA
Table 33-1: 
Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units
Airflow
Type of
interconnecting piping
Diameter of
interconnecting piping
Pitch of
interconnecting piping
Pitch of 
dispersion tubes
Pitch of
header
Horizontal
Steam hose
1½" (DN40) 
2" (DN50)
2"/ft (15%) 
toward Rapid-sorb
Vertically 
plumb
1/8”/ft (1%) 
toward 
condensate 
drain
Tubing or pipe
1½" (DN40) 
2" (DN50)
1/8"/ft (1%) 
toward Rapid-sorb
Vertical
Steam hose
1½" (DN40) 
2" (DN50)
2”/ft (15%) 
toward Rapid-sorb
2"/ft (15%) 
toward 
header
1/8”/ft (1%) 
toward 
condensate 
drain
Tubing or pipe
1½" (DN40) 
2" (DN50)
1/8”/ft (1%) 
toward Rapid-sorb
mc_060310_1000