Specifications
Page 32 • DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Dispersion: 
Rapid-sorb
Installation
Important: 
Before marking and drilling holes in the 
duct or air handler, refer to ALL pitch 
requirements for the Rapid-sorb assembly 
you received (see Table 33-1). The size, 
quantity, and location of penetrations 
are determined by the dimensions and 
configuration of the Rapid-sorb assembly 
you received. 
 mc_060210_0937
Read all dispersion instructions in this manual, and follow the 
installation instructions below:
•  Unpack shipment and verify receipt of all Rapid-sorb 
components with packing list. Report any shortages to 
DRI-STEEM immediately. The components typically include the 
following:
–  Multiple dispersion tubes
– Header
–  ¾" × 2" (19 mm × 51 mm) L-bracket
Note: Dispersion tubes, header, and L-bracket are each tagged 
with the customer requested identification number.
–  A single duct escutcheon plate the size of the header
–  Slip couplings or hose cuffs and clamps
–  Accessories such as duct plates, slip couplings, or hose cuffs
–  Bolts and washers for mounting the dispersion tubes to the 
bracket
•  L-bracket mounting holes (see note at left): 
–  L-bracket 50" (1270 mm) long or shorter has a mounting hole 
4" (100 mm) from each end for mounting the L-bracket to 
the duct or air handler wall.
–  L-bracket longer than 50" (1270 mm) has an additional 
mounting hole in the center. 
Note: Hardware for mounting the L-bracket to the duct or air 
handler wall and the hardware for the header support 
bracket is not provided.
•  Select an installation location that provides necessary access in 
and around the ductwork or air handler.
•  The Rapid-sorb typically is installed centered side to side in a 
duct, or is installed across the face of a coil in an air handler.
•  The center line of the outer dispersion tubes should never be 
closer than 4.5" (114 mm) from the side of the ductwork or air 
handler wall.
•  The following instructions are for a typical Rapid-sorb 
installation — horizontal-airflow duct with Rapid-sorb header 
either inside or outside the duct. See the Dri-calc Installation 
Guides library or contact your representative/distributor or 
DRI-STEEM for installation instructions for air handler or 
vertical airflow applications.
mc_060210_0945-NA
Important:
Failure to follow the recommendations in 
this section can result in excessive back 
pressure on the humidifier. This will result 
in unacceptable humidification system 
performance such as leaking gaskets, blown 
water seals, erratic water level control, and 
spitting condensate from the dispersion 
tube.
mc_060210_0843
WARNING
Hot surface and steam hazard
Dispersion tube, steam hose, tubing, or 
hard pipe can contain steam, and surfaces 
can be hot. Discharged steam is not 
visible. Contact with hot surfaces or air 
into which steam has been discharged can 
cause severe personal injury.
mc_060110_1555