Specifications
Page 30 • DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Dispersion:
Single dispersion tube
Figure 30-1:
Single dispersion tube without condensate drain
Single dispersion tube without
condensate drain
Mounting nut
3/8" - 16 (M10)
XT humidifier
Duct
Secure and seal
escutcheon plates
90° long sweep or
two 45° elbows
See the first bullet in
Installation notes.
Tube pitch: 2"/ft (15%)
OM-7365X
Pitch*
Steam hose, tubing or pipe (tubing
or pipe must be grounded). Insulate
tubing and hard pipe to reduce
steam loss. Do not insulate steam
hose. See Table 24-1 for maximum
piping lengths.
Dimension A:
3.25" (82.5 mm) for 1½" tubes
Dispersion tube escutcheon plate
OM-351-1
A
A
Dashed lines indicate provided by installer.
* Pitch steam hose, tubing, or pipe
toward humidifier:
– 2"/ft (15%) when using steam
hose
– ½"/ft (5%) when using 1½"
tubing or pipe
mc_062810_0720-XT
Adapter
Installation