Specifications
DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 27
Installation
Dispersion: 
Interconnecting piping requirements
Figure 27-1:
Piping connections to Single dispersion tube, Rapid-sorb, and Ultra-sorb Model LV or LH dispersion assemblies
2” (DN50) 
steam hose
Stainless steel 
Y connector* 
Hose 
clamp*
* Stainless steel Y connector, two 1½” (DN40) hoses, and four hose 
clamps ship with each XT-100 humidifier.
Hose clamp*
Stainless steel tube 
connector*
*  Stainless steel tube connector, one 2" (DN50) hose, and two hose 
clamps ship with each XT-150 humidifier.
*  Stainless steel tube connector, two stainless steel Y-connectors, four 1½” (DN40) hoses, 
and eight hose clamps ship with each XT-200 humidifier.
OM-7621
For multiple cylinders, connect the stainless steel tube connector (provided 
with XT models 150 and 200; available for staged XT humidifiers) directly 
to the dispersion inlet. The diameter and pitch of the tube connector 
must match the inlet diameter and pitch of the dispersion unit. Connect a 
maximum of two cylinders to the tube connector with steam hose, tubing, 
or pipe.
OM-7619
XT-100
1½” (DN40)
steam hose*
XT-150
OM-7620
1½” (DN40)
steam hose*
2” (DN50) steam hose attached 
directly to dispersion (see inset 
below)
Hose clamp*
Stainless steel 
Y connector* 
Hose 
clamp*
1½” (DN40) steam 
hose* 
2” (DN50) steam 
hose 
Stainless steel tube 
connector*
3” (DN80) flange connection 
attached directly to dispersion 
(see inset at right)
XT-200
Connecting multiple cylinders to a dispersion assembly
1½” (DN40)
steam hoses from multiple cylinders
2” (DN50) 
steam hose connection
3” (DN80) 
flange connection
2” (DN50) steam 
hoses from multiple 
cylinders
OM-7625
OM-7624
mc_091010_0938
To dispersion assembly
Pitch steam hose 2”/ft (15%) 
toward dispersion assembly.