Warnings and cautions
CAUTION
Hot discharge water
Discharge water can be as hot as 212 °F (100 °C) and can damage the drain plumbing.
Humidifiers equipped with a water tempering device need fresh make-up water in order to function properly. Make sure the
water supply to the water tempering device remains open during draining.
If the humidifier is not equipped with a water tempering device, allow the tank to cool before opening the drain valve.
Excessive supply water pressure
Supply water pressure greater than 80 psi (550 kPa) can cause the humidifier to overflow.
WARNING
Disconnect electrical power
Disconnect electrical power before installing supply wiring or performing service or maintenance procedures on any
part of the humidification system. Failure to disconnect electrical power could result in fire, electrical shock, and other
hazardous conditions. These hazardous conditions could cause property damage, personal injury, or death.
Contact with energized circuits can cause property damage, severe personal injury, or death as a result of electrical
shock or fire. Do not open control cabinet or remove heater terminal or subpanel access panels until electrical power
is disconnected.
Follow the shutdown procedure in this manual before performing service or maintenance procedures on any part of
the system.
mc_011909_1135
Electrical shock hazard
If the humidifier starts up responding to a call for humidity during maintenance, severe bodily injury or death from
electrical shock could occur. To prevent such start-up, follow the procedure below before performing service or
maintenance procedures on this humidifier:
1. Use Vapor-logic
®
4 keypad/display to drain the cylinder.
2. Use Vapor-logic
®
4 keypad/display to change control mode to Standby.
3. Shut off all electrical power to humidifier using field-installed fused disconnect, and lock all power disconnect
switches in OFF position.
4. Close field-installed manual water supply shut-off valve.
mc_050808_1540