DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 21
Installation
Proper wiring prevents electrical noise.
Electrical noise can produce undesirable effects 
on electronic control circuits, which affects 
controllability. Electrical noise is generated 
by electrical equipment such as inductive 
loads, electric motors, solenoid coils, welding 
machinery, or fluorescent light circuits. The 
electrical noise or interference generated from 
these sources (and the effect on controllers) 
is difficult to define, but the most common 
symptoms are erratic control or intermittent 
operational problems.
Important:
•  For maximum EMC effectiveness, wire all 
humidity, high limit, and airflow controls 
using multicolored shielded/screened plenum-
rated cable with a drain wire for the shield/
screen. Connect the drain wire to the shield/
screen ground terminal with wire less than 
2" (50 mm) in length.
•  Do not ground shield at the device end.
Earth grounding requirements 
A safety earth grounding system that meets national, state, and 
local electrical codes is required. The ground connection must be 
made with solid metal-to-metal connections. Ground wire should 
be the same size as power wiring.
Humidifier wiring