Specifications

DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 17
Installation
Piping:
XT steam blowers
Figure 17-1:
Piping from XT humidifier steam cylinders to XTSBs with Y connectors
OM-7604
OM-7605
Hose clamp (provided)
Hose clamp (provided)
Condensate hose (provided)
Plastic tie
Plastic tie
1½” (DN40) steam hose (provided)
Pitch 2”/ft (15%) minimum
Hose clamp
(provided)
Hose clamp (provided)
Condensate hose
(provided)
Plastic tie
Plastic tie
Hose clamp
Y connector (provided)
Hose clamp
Y connector (provided)
1½” DN40 steam hose
(provided)
To open drain or
humidifier fill cup*
To open drain or
humidifier fill cup*
To open drain or
humidifier fill cup*
To open drain or
humidifier fill cup*
* Water seal is required, whether condensate is piped
to open drain or returned to humidifier fill cup.
Maximum recommended distance between
humidifier and XTSB is 10” (3 m).
mc_091010_0940
7” (178 mm)
water seal
7” (178 mm)
water seal
Pitch 2”/ft (15%)
minimum
XT-75
XT-150
XTSB-50
XTSB-50