Specifications

33
VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Dispersion:
Note:
See Page 36 for steam supply and
condensate drain line connection instructions.
INSTALLATION
Rapid-sorb
4. Position the flange of the L-bracket so it is upstream of the tubes when
the assembly is raised and fastened into position. Fasten the L-bracket
to the end of the dispersion tubes with the provided bolt, lock washer,
and flat washer.
5. Before tightening the L-bracket bolts to the dispersion tubes:
For 1½" (DN40) dispersion tubes:
Dispersion tube will rotate in slip coupling. Verify that dispersion tube
orifices are directed perpendicular to airflow.
Dispersion tube and slip coupling must be fully engaged on header
stub for O-rings to provide a seal.
For 2" (DN50) dispersion tubes:
Before securing hose cuff in place with hose clamps on dispersion tube
and the header stub, verify that dispersion tube orifices are directed
perpendicular to airflow.
6. Slide the assembly up until the L-bracket aligns with the mounting holes in
the duct.
For 1½" (DN40) dispersion tubes:
Header pitch is duplicated in the L-bracket.
Dispersion tube and slip coupling must be fully engaged on header
stub for O-rings to provide a seal.
High end of L-bracket can be fastened tight to duct or air handler.
Fastener on low end of L-bracket must be long enough to compensate
for pitch. Use a nut on both sides of L-bracket and duct or air handler
for stability.
For 2" (DN50) dispersion tubes:
Fasten bracket to top of duct and use hose cuffs to compensate for
header pitch.
Before securing hose cuffs with hose clamps on dispersion tube and
header stub, verify that header pitch, 1/8"/ft (1%) toward drain, is
maintained.
7. Permanently secure both ends of header, and verify that header pitch,
1/8"/ft (1%) toward drain, is maintained.
8. Verify that all fasteners are secure:
L-bracket to duct
Dispersion tubes to L-bracket
Hose clamps on 2" (DN50) tubes
9. Secure and seal the dispersion tube escutcheon plate and condensate
drain tube escutcheon plate around the respective tubes, if applicable.
mc_060210_1015-NA