Specifications

27
VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Dispersion:
INSTALLATION
Table 27-1:
SDU-E minimum nonwetting distances
kW
Maximum steam
capacity
40% RH @ 70 °F (21 °C) 50% RH @ 70 °F (21 °C) 60% RH @ 70 °F (21 °C)
Rise Spread Throw Rise Spread Throw Rise Spread Throw
lbs/hr kg/h ft m ft m ft m ft m ft m ft m ft m ft m ft m
2 6 2.7 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
4 12 5.4 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
6 18 8.2 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
8 24 10.9 1.0 0.3 1.0 0.3 5.5 1.7 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
10 30 13.6 1.5 0.5 1.5 0.5 6.0 1.8 2.0 0.6 2.0 0.6
7.0 2.1 3.0 1.0 3.0 1.0 8.0 2.5
12 36 16.3 1.5 0.5 1.5 0.5 6.0 1.8 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 8.0 2.5
14 42 19.1 2.0 0.6 2.0 0.6 7.0 2.1 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 9.0 2.7
16 48 21.8 2.0 0.6 2.0 0.6 7.0 2.1 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 9.0 2.7
21 63 28.6 2.0 0.6 2.0 0.6 7.5 2.3 2.5 0.8 2.5 0.8 10.0 3.0 3.0 1.0 3.0 1.0 12.0 3.7
25 75 34.0 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8
30 90 40.9 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8
34 102 46.3 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8
Notes:
• Surfaces or objects directly in the path of steam discharge may cause condensation and dripping.
• To avoid steam impingement on surrounding areas, observe the minimum nonwetting dimensions in this table.
• Rise: The minimum nonwetting height above the steam outlet of the SDU-E.
• Spread: The minimum nonwetting width from the steam outlet of the SDU-E.
• Throw: The minimum nonwetting horizontal distance from the steam outlet of the SDU-E.
mc_042710_1300-NA
SDU-I and SDU-E