Specifications

24
VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Dispersion:
INSTALLATION
Humidified air
discharge grille
24.2"
(615 mm)
18.6"
(472 mm)
10.9"
(276 mm)
1½" (DN40)
steam inlet
Front view Side view
16.1"
(409 mm)
Air intake
grille
2.25" (57 mm)
DC-1076
Steam
outlet
24.2"
(615 mm)
18.6"
(472 mm)
10.9"
(276 mm)
1½" (DN40)
or 2" (DN50)
steam inlet
Front view Side view
16.1"
(409 mm)
Steam inlet
2.25"
(57 mm)
DC-1078
3/4" (DN20) pipe thread
drain nipple (see note below)
3.2" (82 mm)
Note: SDU-E dispersion box requires an installed condensate drain line and water seal, provided
by installer. See Figure 25-1.
mc_052510_1700-NA
mc_052510_1701-NA
Table 24-1:
SDU specifications
SDU model
Maximum capacity Shipping weight
Amps at 120V
(50/60 Hz)
Horsepower cfm m
3
/s dB*
lbs/hr kg/h lbs kg
SDU-I 30 13.6 68 31 3.20 1/5 760 0.36 58
SDU-E 102 46.3 61 28 2.07 1/8 545 0.26 64
* Measurement taken 6.5' (2 m) in front of SDU cabinet.
mc_042710_1440-NA
SDU-I and SDU-E
FIGURE 24-1: SDU-I MECHANICAL DETAIL
FIGURE 24-2: SDU-E MECHANICAL DETAIL