Specifications
9
VAPORMIST
®
WIRING
VAPORMIST wiring
All wiring must be in accordance with all governing
codes, and with the VAPORMIST or VAPORMIST DI
wiring diagram. The diagrams are located inside the
removable subpanel cover on the right side of the
humidifier cabinet. Power supply wiring must be rated
for 105 °C.
When selecting a location for installing the
VAPORMIST, avoid areas close to sources of
electromagnetic emissions such as power distribution
transformers.
The use of semiconductor fusing sized per the National
Electric Code is recommended with the SSR option.
Grounding requirements
The earth must be made by solid metal to metal
connections. The ground must be a good radio
frequency earth. Ground wire should be same size as
power wiring.
Shielded/screened cable drain wire connection to lug
Note: For maximum EMC effectiveness, all humidity, temperature, and airflow controls should be wired using
multicolored shielded/screened plenum-rated cable with a drain wire for the shield/screen. The drain wire should
be connected to the shield/screen ground terminal with its length kept to less than 2".
Shield/screen ground lug
Microprocessor
board
VAPOR-LOGIC
3
keypad on front of
cabinet
OM-1505
Field wiring requirements
Note: Control wiring and power wiring must be run in
dedicated or separate earthed metal conduit, cable
trays or trunking.
OM-1007
Fused disconnect
(provided by
installer)
Power supply
(provided by
installer)
Right side view of VAPORMIST