Specifications

17
VAPORMIST
®
DISPERSION
Description
Nominal hose, tubing
or pipe size
Steam loss
Insulation thickness
Noninsulated Insulated
inches DN lbs/hr/ft kg/h/m lbs/hr/ft kg/h/m inches mm
Hose
40 0.15 0.22 N/A N/A N/A N/A
2 50 0.20 0.30 N/A N/A N/A N/A
Tubing
40 0.11 0.164 0.02 0.03 2 50
2 50 0.14 0.21 0.025 0.037 2 50
Pipe
40 0.22 0.33 0.02 0.03 2 50
2 50 0.25 0.38 0.025 0.037 2 50
Steam loss of interconnecting vapor hose, tubing and pipe
Notes:
This data is based on an ambient air temperature of 80 °F (27 °C), fiberglass insulation, copper tubing, and
Schedule 40 pipe.
Maximum steam carrying capacity and length of
interconnecting vapor hose, tubing and pipe*
Vapor hose
Copper or stainless steel tubing
and Schedule 40 steel pipe
Hose I.D. Maximum capacity Maximum length**
Tube or
pipe size***
Maximum capacity
Maximum
developed length
inches DN lbs/hr kg/h ft m inches DN lbs/hr kg/h ft m
40 150 68 10 3 40 150 68 20 6.1
2 50 250 113 10 3 2 50 220 100 30 9.2
Notes:
* Based on total maximum pressure drop in hose, tubing or piping of 5" wc (1250 Pa)
** Maximum recommended length for vapor hose is 10' (3 m). Longer distances may cause kinking or low spots.
*** To minimize loss of capacity and efficiency, insulate tubing and piping.
Developed length equals measured length plus 50% of measured length, to account for pipe fittings.
VM99-C-0302.pdf 17 11/19/2009 9:51:32 AM