Specifications
16
VAPORMIST
®
DISPERSION
Drip tee installation
Install a drip tee as shown below when the humidifier is mounted higher than the dispersion device, when
interconnecting hose or piping needs to go over an obstruction, or when interconnecting piping runs are long.
IMPORTANT: Vapor hose must be supported to prevent sagging or low spots.
Obstruction
Pitch: 1/8"/ft (1%)
VAPORMIST
humidifier
Funnel or floor drain.
Refer to governing codes for drain
pipe size and maximum temperature
requirements.
1" (25 mm) air gap
8" (200 mm) minimum
6" (150 mm) recommended
To dispersion device
DC-1450
Dashed lines indicate
provided by installer.
3/4" (DN20)
90° long sweep or
two 45° elbows
Insulate tubing and hard
pipe to reduce steam loss
Tubing or pipe drip tee, by installer.
DRI-STEEM part numbers for
304 stainless steel inline tees:
• 1½" (DN40): No. 162710
• 2" (DN50): No. 162712
VM99-C-0302.pdf 16 11/19/2009 9:51:32 AM










