Specifications

%3*45&&.7BQPSNJTU&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBMt1BHF
Figure 7-1:
Clearance recommendations
Top (when SDU is not mounted directly
above the Vapormist): 18"(460 mm)
Supporting wall
Front 36" (915 mm)
Floor: 24" (610 mm)
Left side:
12" (305 mm)
Secured to
supporting wall
To dispersion assembly
DC-1201
Mounting the humidifier on the wall
When mounting on a wood stud wall (studs 16" [406 mm] on
center), locate studs and position lag bolts in place so that each of
the bolts centers on a stud. Mark hole locations and predrill ¼"
(6 mm) diameter pilot holes. Secure cabinet to wall with lag bolts
provided.
When mounting on a metal stud wall, locate the studs (16"
[406 mm] on center) and drill a 3/8" (10 mm) hole through the
studs and wall. Push a 3/8" (10 mm) bolt through the wall, studs,
and a backing plate on the backside of the wall and secure with a
nut and washer.
If 16" (406 mm) on-center studs are not available, mount spanner
boards on the wall, spanning two studs. If two horizontal boards are
used, locate one at the top of the cabinet for the lag bolts and the
other board located 3" (76 mm) on center from the bottom of the
cabinet.
For hollow block or poured concrete wall mounting, position
template in place and mark the holes. Drill appropriate pilot holes
for two 3/8" (10 mm) toggle bolts or two 3/8" (10 mm) machine
bolt lead anchors. Secure cabinet in place.
.PVOUJOHUIFIVNJEJGJFS
WARNING!
Mount humidifier per the instructions in this
manual and to a structurally stable surface.
Improper mounting of humidifier can cause
the humidifier to fall off the wall resulting in
severe personal injury or death.
Right side electrical
controls: 36" (915 mm)
VM-IOM-1108.pdf 9 4/21/2010 1:36:20 PM