Specifications
1BHFt%3*45&&.7BQPSNJTU&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBM
%JTQFSTJPO4JOHMFUVCF
/PUFT
t 6TF%3*45&&.TIBSEQJQFBEBQUFSLJUUPDPOOFDUUIFTUFBN
outlet to hard pipe. Use a hose clamp to connect the steam outlet
to vapor hose. Use a hose cuff and clamps to connect the steam
outlet to tubing.
t 5IJOXBMMFEUVCJOHIFBUTVQGBTUFSUIBOIFBWZXBMMFEQJQF
causing less steam loss at start-up.
t )BSEQJQFPSUVCJOHEJBNFUFSNVTUNBUDI7BQPSNJTUTUFBN
outlet size 1½" (DN40) or 2" (DN50).
t 4FFUIF.BYJNVN4UFBN$BSSZJOH$BQBDJUZBOE4UFBN-PTT
tables on Page 16.
t .BYJNVNDBQBDJUZPGEJTQFSTJPOUVCFXJUIPVUDPOEFOTBUF
drain):
– 1½" (DN40): 28.4 lbs/hr (13 kg/h)
– 2" (DN50): 56.8 lbs/hr (25.8 kg/h)
t 0SJFOUEJTQFSTJPOUVCFTPUIBUUVCFMFUTTUFBNPSJGJDFTQPJOUVQ
t 8IFONPVOUJOHUIFIVNJEJGJFSBCPWFUIFMFWFMPGEJTQFSTJPO
tube, see the drawing on Page 17.
t 'BJMVSFUPGPMMPXUIFSFDPNNFOEBUJPOTPOUIJTQBHFDBOSFTVMU
in excessive back pressures on the humidifier. This can lead to
dispersion tube(s) spitting, steam blowing through water seals, or
leaking gaskets.
t 5BCMFTIPXTIPTFLJUTJ[FTCZIVNJEJGJFSNPEFM"IPTF
kit includes vapor hose, a dispersion tube and hardware. Note
that the capacities of models VM-30 and VM-34 require multiple
tube assemblies and therefore cannot use a hose kit. For multiple
tube assemblies, see information on Rapid-sorb on pages 24-30.
Figure 22-1:
Single tube without condensate drain
Single dispersion tube
without condensate drain
Mounting nut
3/8" - 16 (M10)
Vapormist
humidifier
Duct
Secure and seal
escutcheon plates
90° long sweep or
two 45° elbows
See the first bullet in
the notes below.
Tube pitch: 2"/ft (15%)
DC-1447
Table 22-1:
Hose kit sizing by model
Humidifier
models
Hose kit
(vapor hose,
dispersion tube
and hardware)
Maximum capacity
of dispersion tube
lbs/hr kg/h
VM 2-8
1½" (DN40) hose
kit without drain
28.4 13
VM 10-16
1½" (DN40) hose
kit with drain
56.8 25.8
2" (DN50) hose
kit without drain
56.8 25.8
VM 21-25
2" (DN50) hose
kit without drain
85.2 38.6
VM 30-34
These models require multiple tube
assemblies and cannot use a hose kit.
WARNING!
Dispersion tube, vapor hose, tubing, or hard
pipe can contain steam, and surfaces can be
hot. Discharged steam is not visible. Contact
with hot surfaces or air into which steam has
been discharged can cause severe personal
injury.
Pitch*
Notes:
* Pitch vapor hose,
tubing or pipe toward
humidifier:
– 2"/ft (15%) when
using vapor hose
– 1/8"/ft (1%) when
using tubing or pipe
t %BTIFEMJOFTJOEJDBUF
provided by installer
Vapor hose, tubing or
pipe. Insulate tubing
and hard pipe to reduce
steam loss. Do not
insulate vapor hose. See
Table 16-1 for maximum
piping lengths.
Dimension A:
t NNGPSUVCFT
t NNGPSUVCFT
Dispersion tube escutcheon plate
OM-351-1
A
A