Specifications
%3*45&&.7BQPSNJTU&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBMt1BHF
Figure 17-1:
Drip tee installation
%JTQFSTJPO%SJQUFFJOTUBMMBUJPO
Drip tee installation
Install a drip tee as shown below when the humidifier is mounted
higher than the dispersion assembly, when interconnecting hose or
piping needs to go over an obstruction, or when interconnecting
piping runs are long.
Important: Vapor hose must be supported to prevent sagging
or low spots.
WARNING!
Dispersion tube, vapor hose, tubing, or hard
pipe can contain steam, and surfaces can be
hot. Discharged steam is not visible. Contact
with hot surfaces or air into which steam has
been discharged can cause severe personal
injury.
DC-1450
90° long sweep or two 45° elbows
Obstruction
Insulate tubing and hard
pipe to reduce steam loss
To dispersion assembly
6" (150 mm) recommended
8" (200 mm) minimum
1" (25 mm) air gap
Open funnel or floor drain.
See first note below.
¾" (DN20)
Tubing or pipe drip tee, by installer.
DRI-STEEM part numbers for
304 stainless steel inline tees:
t %//P
t %//P
Pitch
Vapormist
humidifier
Notes:
t -PDBUFBJSHBQPOMZJOTQBDFTXJUIBEFRVBUFUFNQFSBUVSFBOEBJSNPWFNFOUUPBCTPSCnBTITUFBNPUIFSXJTFDPOEFOTBUJPONBZGPSNPOOFBSCZTVSGBDFT3FGFS
to governing codes for drain pipe size and maximum discharge water temperature.
t 4VQQPSUWBQPSIPTFTPUIFSFBSFOPTBHTPSMPXTQPUT
t %BTIFEMJOFTJOEJDBUFQSPWJEFECZJOTUBMMFS
VM-IOM-1108.pdf 19 4/21/2010 1:36:21 PM