Connecting humidifier to dispersion assembly with tubing or
pipe (continued)
t *OTVMBUJOHIBSEQJQFSFEVDFTUIFMPTTJOPVUQVUDBVTFECZ
condensation.
t 8IFOVTJOHIBSEQJQFUBLFDBSFUPSFNPWF"--USBDFTPG
lubricants used to thread the pipe. This will minimize the
possibility of tank foaming. Denatured alcohol or mineral spirits
work best for removing lubricant.
t *GUIFIVNJEJGJFSNVTUCFMPDBUFEBCPWFUIFEJTQFSTJPOBTTFNCMZ
use the recommend installation as shown on Page 17.
t 4FFUIFNBYJNVNTUFBNDBSSZJOHDBQBDJUZUBCMFCFMPX
%JTQFSTJPO*OUFSDPOOFDUJOHQJQJOH
SFRVJSFNFOUTDPOUJOVFE
Table 16-1:
Maximum steam carrying capacity and length of interconnecting vapor hose, tubing and pipe*
Vapor hose Copper or stainless steel tubing and Schedule 40 steel pipe
Hose I.D. Maximum capacity Maximum length** Tube or pipe size***
Maximum
capacity
Maximum
developed length
inches DN lbs/hr kg/h ft m inches DN lbs/hr kg/h ft m
40 150 68 10 3 40 150 68 20 6.1
2 50 250 113 10 3 2 50 220 100 30 9.2
/PUFT
* Based on total maximum pressure drop in hose, tubing or piping of 5" wc (1250 Pa)
** Maximum recommended length for vapor hose is 10' (3 m). Longer distances can cause kinking or low spots.
*** To minimize loss of capacity and efficiency, insulate tubing and piping.
Developed length equals measured length plus 50% of measured length, to account for pipe fittings.