Specifications
%3*45&&.7BQPSNJTU&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBMt1BHF
Connecting humidifier to dispersion assembly with vapor hose
t "MXBZTTVQQPSUWBQPSIPTFUPQSFWFOUTBHTPSMPXTQPUTBOEUP
maintain a minimum pitch of 2"/ft (15%) back to the humidifier.
t 4FFUIFNBYJNVNTUFBNDBSSZJOHDBQBDJUZUBCMFPOUIFOFYUQBHF
t 6TF%3*45&&.WBQPSIPTF0UIFSNBOVGBDUVSFSTPGWBQPS
hose may use unacceptable release agents or material mixes
that can affect humidifier system performance adversely. Using
hose from alternative manufacturers increases the possibility of
tank foaming and accelerated aging. Foaming causes condensate
discharge at the dispersion assembly.
t %POPUVTFWBQPSIPTFJOPVUEPPSBQQMJDBUJPOT
t %POPUJOTVMBUFWBQPSIPTF*OTVMBUJPODBVTFTBDDFMFSBUFEIFBU
aging, causing the vapor hose to become hard and susceptible to
failure due to cracks.
t 5IFTUFBNPVUMFUPOUIFIVNJEJGJFSJTTJ[FEUPUIFPVUQVUPGUIF
humidifier. DO NOT use hose with an inside diameter (ID)
smaller than the humidifier steam outlet.
t *GUIFIVNJEJGJFSNVTUCFMPDBUFEBCPWFUIFEJTQFSTJPOBTTFNCMZ
use the recommend installation as shown on Page 17.
t 'PSTJOHMFUVCFBQQMJDBUJPOTTFFUIFIPTFLJUTJ[JOHDIBSUPO
Page 22.
Connecting humidifier to dispersion assembly
with tubing or pipe
t 4FFUIFGPMMPXJOHQBHFTGPSJOUFSDPOOFDUJOHUVCJOHBOEQJQFQJUDI
requirements for specific applications.
t 5IFTUFBNPVUMFUPOUIFIVNJEJGJFSJTTJ[FEUPUIFPVUQVUPGUIF
humidifier. DO NOT use interconnecting tubing or pipe with an
inside diameter (ID) smaller than the humidifier steam outlet.
t 4UFBNTVQQMZBEBQUFSTBSFBWBJMBCMFGSPN%3*45&&.5IFTF
adapters convert a tubing outlet on the humidifier to threaded
pipe, allowing a pipe connection.
t ¡FMCPXTBSFOPUSFDPNNFOEFEVTFUXP¡FMCPXThN
apart.
t 5IJOXBMMUVCJOHIFBUTVQGBTUFSBOEDBVTFTMFTTTUBSUVQMPTTUIBO
heavy wall pipe.
%JTQFSTJPO*OUFSDPOOFDUJOHQJQJOH
SFRVJSFNFOUT
Important:
Failure to follow the recommendations in
this section can result in excessive back
pressures on the humidifier. This will result
in unacceptable humidification system
performance such as leaking gaskets, blown
water seals, erratic water level control, and
spitting condensate from the dispersion
tube(s).
.PSFPOUIFOFYUQBHFȚ
Important:
Reducing the inside diameter of the
interconnecting piping will result in
the internal humidifier system pressure
exceeding the parameters for acceptable
performance.
VM-IOM-1108.pdf 17 4/21/2010 1:36:21 PM