Specifications
DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual • Page 49
Maintenance
Table 49-1:
CRUV subpanel with Vapor-logic4 option
Item Description Qty Part No.
1 Main controller, Vapor-logic4 1 408495-001
2 PC board support, locking 4 409591-004
3
Transformer, 600V, 24 VAC Sec, 75 VA * 1 408986
Transformer, 277V, 24V Sec 75 VA * 1 408982
Transformer, 120/208/240/480V 24V Sec * 1 408965-001
4
Contactor, 55A (Siemens) * 1 407010-002
Contactor, 35A (Siemens) * 1 407010-001
5 Power block, 3 pole 1 408300-002
6 Relay, 24V DPDT, finder 1 407900-016
7 Relay socket, DPDT, without time delay 1 407900-019
8 Terminal, 20A, DIN rail mount * 408252-001
9 Switch, door interlock, electric (optional) * 1 408470
10 Bracket, door interlock, small (optional) 1 165614
11 Fan, cooling, 24” (610 mm) leads 1 405800-054
12
SSR, 2 pole, Carlo Gavazzi, 600V * 408677-004
SSR, 2 pole, Carlo Gavazzi, 480V/50 Amp * 408677-003
SSR, 1 pole, Carlo Gavazzi, 480V/63 Amp * 408677-005
SSR, 1 pole, Carlo Gavazzi, 480V * 408677-002
13
Enclosure, JIC, 20" x 20" x 7"
(508 mm x 508 mm x 178 mm) *
1 407100-007
Enclosure, NEMA-4, 20" x 20" N4-20206
(508 mm x 508 mm), (optional) *
1 408150-004
* Specify humidifier model and serial numbers when ordering replacement parts.
Replacement parts:
CRUV subpanel with Vapor-logic4
option