DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual • Page 33
Tap/softened water
Table 33-1: 
Skim time settings
Dip switch
Skim time
45
Option Off Off 3 seconds
Option On Off 9 seconds
Factory 
settings
Off On 32 seconds
Option On On 45 seconds
The best way to determine how often your humidifier needs 
maintenance is to remove the tank cover and inspect it for mineral 
deposits after three months of duty. Hours of operation and duty 
cycle will determine your maintenance schedule, as will water 
quality.
Water quality and maintenance
Maintenance requirements vary with water quality, because tap and 
softened water carry a variety of minerals and other materials in a 
mix that varies from location to location. Very hard (high mineral 
content) water requires more frequent cleaning and drain/flush 
cycles than water with low mineral content.
Softened water significantly reduces mineral accumulation inside 
the humidifier.
Note: S
olids, like silica, are not removed in the softening process.
Skim duration
Skim duration determines the quantity of water skimmed with each 
fill cycle and is field adjustable:
•  LW series controller, dip switches on controller board 
(see Table 33-1)
•  Optional Vapor-logic4 controller, keypad/display or web 
interface (see Vapor-logic4 Installation and Operation Manual)
Skimming reduces the need for frequent humidifier cleaning. 
Each time the tank refills, it fills to a level just above the lip of the 
skim/overflow fitting. A portion of the fill water flows out of the 
skim/overflow fitting to the drain, which flushes minerals left by the 
previous evaporating cycle and skims away surface residue.
Both humidifier cleaning and heated water flowing to the drain are 
operational costs. DRI-STEEM recommends that the user observe 
and adjust the skim duration to achieve a balance between reducing 
mineral buildup and conserving heated water.
mc_060210_1430-CRUV
WARNING
Electric shock hazard
Contact with energized circuits 
can cause severe personal injury or 
death as a result of electric shock. To 
prevent shock, disconnect electrical 
power before performing service or 
maintenance procedures on an part of 
the humidification system.
When performing maintenance on the 
humidifier:
• If the humidifier is equipped with a 
Vapor-logic4 controller, use the keypad 
to change the control mode to Standby.
• Place all power disconnects in OFF 
position and lock in OFF position.
• Close the field-installed manual supply 
water shut-off valve.
mc_031110_0444-CRUV
Maintenance