Specifications
Page 28 • DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual
Start-up checklist
LW series controller
Tap/softened water 
☐  Adjust humidistat setting to create a call for humidity.
☐  Open shut-off valve on water supply line, and confirm that 
drain valve is closed. Tank should begin filling with water 
through fill valve.
☐  Shortly before fill valve shuts off, rising water level causes water 
to come in contact with the bottom probe, and heating element 
contactor(s) will be actuated.
☐  Check heater cut-off circuit as follows:
1.  Close manual water supply valve, then open drain valve and 
start draining tank.
2.  When water level drops below bottom probe, the heating 
element contactor(s) drop out.
3.  When Step 2 above has completed, close drain valve.
☐  Check function of field-installed safety controls, such as fan 
proving switch. Contactor(s) should drop out when proving 
switch is open.
☐  Check heater draw by testing and recording voltage and 
amperage in each phase. Readings should match humidifier 
name plate readings (name plate is on humidifier housing).
☐  Inspect installation for steam or air leaks while operating 
humidifier. Seal any leaks. 
DI/RO water option
☐  Adjust humidistat setting to create a call for humidity.
☐  Open shut-off valve on water supply line, and confirm that 
drain valve is closed. Tank should begin filling with water 
through fill valve.
☐  Shortly before fill valve shuts off, float-operated heater cut-off 
switch will “make,” and heating element contactor(s) will be 
actuated. A time delay relay circuit prevents contactor chatter 
that would otherwise occur due to bouncing of heater cut-off 
float.
☐  Check heater cut-off circuit as follows:
1.  Close manual water supply valve, then open drain valve and 
start draining tank.
2.  When water level drops past switching level on heater cut-off 
float, the heating element contactor(s) drop out.
3.  When Step 2 above has completed, close drain valve.
☐  Check function of field-installed safety controls, such as fan 
proving switch. Contactor(s) should drop out when proving 
switch is open.
☐  Check heater draw by testing and recording voltage and 
amperage in each phase. Readings should match humidifier 
name plate readings (name plate is on humidifier housing).
☐  Inspect installation for steam or air leaks while operating 
humidifier. Seal any leaks.