Specifications

Page 8 • DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual
Piping:
Tap/softened water
Installation
Figure 8-1:
CRUV (tap/softened water) field piping overview
Notes:
Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and maximum discharge water temperature.
Offset humidifier from floor drain to prevent flash steam from rising into the humidifier.
Dashed lines indicate provided by installer.
The water supply inlet is more than 1" (25 mm) above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No
additional backflow prevention is required; however, governing codes prevail.
Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
Install plumb
DC-1133
Steam vapor hose
Shock arrester recommended
to reduce water hammer
Skim/overflow port
Drain
If run is over 10' (3 m), increase
pipe to 1¼" (DN32)
1" (25 mm) air gap
Pitch 1/8"/ft (1%)
6" (152 mm)
recommended
Open drain required. See first note below.
Tank surfaces will reach
212 °F (100 °C) when
operating. Provide outer
protection from direct
contact, but allow for
natural ventilation.
Water inlet strainer
Water supply inlet
12" (305 mm)
minimum
¾" (DN20) union for skim, drain, and overflow
connection; plumbing rated for 212 °F (100 °C)
Tank support
Water supply line:
¼" NPT (DN8) connection size
25 to 80 psi (175 to 550 kPa) required water
pressure
First 3’ (1 m) of supply line must be rated for
212 ºF (100 ºC)
If water piping to humidifier is nonmetallic, we
recommend a 2” (50 mm) metallic water seal or loop
in the supply line to isolate steam during maintenance.
mc_071210_1603