Operating instructions
68
Operation
Operation:
Troubleshooting guide
Troubleshooting guide.
Problem
number
Problem Possible cause Action
32
33
Humidity below
desired level
(cont.)
Humidity above set
point
Heating elements
not operating
Humidity control
input type not the
same as
VAPOR-LOGIC
3
software
High entering
relative humidity
Unit oversized
Reduced air flow
Improperly located
humidistat or
humidity
transmitters
If heaters are burned out, refer to
Problem #30 Heater burnout.
Verify that humidistat is calling for
humidity.
Check for control voltage if limit
controls (air flow proving switch, zone
valves, etc.) are not allowing unit to
operate.
Check fuses and replace if they are
blown.
Check if the (optional) heater over-
temperature has been tripped. Reset if
necessary.
Check VAPOR-LOGIC
®
3
control board
connections J26, J27 and J28. Consult
DRI-STEEM.
Dehumidify.
Consult DRI-STEEM.
Check fans, dampers, VAV systems,
etc.
Relocate using guidelines established
in this manual (see Pages 16-23).
More on next page ...