Operating instructions
66
Operation
Operation:
Troubleshooting guide
Troubleshooting guide.
Problem
number
Problem Possible cause Action
31 Noisy operation Thunder-type
noise coming from
tank during refill
Contactor noise
Fill valve noise
Normal on larger units, caused by the
cold fill water collapsing steam in the
tank. Reduce psi (minimum of 25 psi)
if inlet water pressure is too high.
Contactor normally makes a clunk
as it pulls in. A continuous chattering
noise is not normal and is
symptomatic of a failing contactor or
malfunctioning controls. Replace
contactor or troubleshoot the control
system.
A clicking sound as fill valve opens
or closes and a hissing sound during
fill are normal. A slamming sound as
fill valve closes is water hammer
and can be minimized by installing a
shock arrester.
A loud buzzing sound indicates poor
alignment of valve stem. Replace
valve.
More on next page ...