Operating instructions

63
Operation
Operation:
Troubleshooting guide
Troubleshooting guide.
Problem
number
Problem Possible cause Action
27 Fill valve does not
close.
Open drain valve
Malfunctioning level
control system
If automatic drain valve is locked in
manual open position, reset to
automatic.
Replace valve if there is a broken
return spring on the drain valve.
Clean or replace drain valve if an
obstruction in the valve will not allow
complete closure.
Close manual drain valve, if it is open.
If VAPOR-LOGIC
®
3
shorted output to
fill valve coil, replace board.
Check if probe head is fully plugged
in.
If needed, clean probe rod tips.
Verify if VAPOR-LOGIC
3
control
board with nylon mounting standoffs
terminal 33 needs to be grounded.
If there is low water conductivity, add
salt to tank water. (If this solves the
problem, consult DRI-STEEM for
further advice.)
Replace board if VAPOR-LOGIC
3
control board is defective.
Verify that system is in auto mode.
Verify that probe is wired correctly.
Check terminals 30, 31, 32 and 33 on
VAPOR-LOGIC
3
control board
terminal block J8 for correct voltage:
32 (purple) to 33 (yellow),
no water present > 2 VAC
32 (purple) to 33 (yellow),
water present < 1/4 VAC
31 (orange) to 33 (yellow),
same readings as above
30 (brown) to 33 (yellow),
same readings as above