Operating instructions
61
Operation
Troubleshooting guide.
Problem
number
Problem Possible cause Action
24
25
26
Slave # fault
Control does not
energize.
Unit does not fill with
water.
LonTalk
®
communications cable
is not connected
between boards.
Slave board does not
have power or has
incorrect power.
Nonexistent supply
voltage to unit
Nonexistent control
voltage
Heater over-
temperature
thermostat open
Malfunctioning fill
valve
No water supply to fill
valve
Connect LonTalk communications
cable.
Verify power wiring on slave board.
Check main line fuse.
Check main line safety switch.
Check heater fuses.
Check for proper supply.
Verify proper transformer voltage
characteristics.
Verify proper wiring of transformer.
Check for control circuit voltage, 24
VAC. If voltage is not present, check
transformer circuit breaker. Reset if
needed.
Reset manual switch located above
heater or humidifier cover.
First, disconnect brown wire and then
the orange wire from VAPOR-LOGIC
®
3
board terminals 30 and 31 of terminal
block J8. Fill valve should open.
If fill valve does not open, verify
proper 24 VAC (terminals 1 and 2) to
fill valve. If voltage is present and
valve does not open, replace valve or
valve coil.
Verify that coil is 24 VAC.
Verify that valve stem moves freely.
Check if water supply line strainer is
plugged.
Verify that manual water line shut-off
valve is open and that pressure exists.
More on next page ...
Operation:
Troubleshooting guide