Operating instructions
60
Operation
Troubleshooting guide.
Problem
number
Problem Possible cause Action
20
21
22
23
Flue fault
Burner # fault
Ignitor # fault
Blower # fault
The combustion air
damper is incorrectly
wired or has failed to
open.
The power vent
pressure switch is
incorrectly wired or
the power vent has
failed to start.
No gas supply to unit
Gas valve is off or
there is no power to
the valve.
Broken ignitor
Gas valve/ignitor/
sensing electrode is
out of sequence
Gas valve outlet
pressure is too low.
Blower inlet is dirty
or obstructed.
Broken ignitor
Gas valve/ignitor/
sensing electrode is
out of sequence.
The blower is
incorrectly wired or
the blower failed to
start.
Check for proper combustion air
damper wiring.
Check for proper power vent wiring.
Verify that gas service valve is on and
receiving minimum pressure to
manifold per rating plate.
Verify that valve is in on position and
that there is power to the valve.
Verify that ignitor glows.
Verify wire connections to these
components.
Verify out pressure is set per rating
plate.
Clean inlet and check for obstructions.
Verify that ignitor glows.
Verify wire connections to these
components.
Check for proper blower wiring.
More on next page ...
Operation:
Troubleshooting guide