Specifications

Page 22 • DRI-STEEM Vapormist humidifier
Figure 22-1:
SDU-E rise, spread, and throw
Air intake
grille
Steam outlet
Spread
Throw
DC-1027
Rise
As steam is discharged from the SDU-E, it quickly cools and turns
to a visible fog that is lighter than air. As this fog is carried away
from the SDU-E by the airstream, it tends to rise toward the ceiling.
If this fog contacts solid surfaces (columns, beams, ceiling, pipes,
etc.) before it disappears, it could collect and drip as water. The
greater the space relative humidity, the more the fog will rise, throw
and spread.
Table 22-1 lists the minimum rise, throw and spread non-wetting
distances for SDU-E at 40%, 50% and 60% RH in the space.
Surfaces cooler than ambient temperature, or objects located within
this minimum dimension, can cause condensation and dripping.
To avoid steam impingement on surrounding areas, observe the
minimum non-wetting distances in Table 22-1.
The SDU-E contains a blower (120 V, single-phase, 60 Hz) and
anairflow proving switch (field-wired to the humidifier electrical
panel). A wiring diagram of the SDU-E is included with the unit.
On a call for humidity, the humidifier begins producing steam,
and the start relay energizes the SDU-E blower. When the call for
humidity is satisfied, the Vapor-logic4 controller keeps the blower
running to disperse residual moisture using a time delay.
mc_042710_1255
Table 22-1:
SDU-E minimum nonwetting distances
kW
Maximum
steam capacity
40% RH @ 70 °F (21 °C) 50% RH @ 70 °F (21 °C) 60% RH @ 70 °F (21 °C)
Rise Spread Throw Rise Spread Throw Rise Spread Throw
lbs/hr kg/h ft m ft m ft m ft m ft m ft m ft m ft m ft m
2 6 2.7 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
4 12 5.4 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
6 18 8.2 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
8 24 10.9 1.0 0.3 1.0 0.3 5.5 1.7 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3
10 30 13.6 1.5 0.5 1.5 0.5 6.0 1.8 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 8.0 2.5
12 36 16.3 1.5 0.5 1.5 0.5 6.0 1.8 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 8.0 2.5
14 42 19.1 2.0 0.6 2.0 0.6 7.0 2.1 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 9.0 2.7
16 48 21.8 2.0 0.6 2.0 0.6 7.0 2.1 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 9.0 2.7
21 63 28.6 2.0 0.6 2.0 0.6 7.5 2.3 2.5 0.8 2.5 0.8 10.0 3.0 3.0 1.0 3.0 1.0 12.0 3.7
25 75 34.0 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8
30 90 40.9 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8
34 102 46.3 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8
Notes:
• Surfaces or objects directly in the path of vapor discharge may cause condensation and dripping.
To avoid steam impingement on surrounding areas, observe the minimum nonwetting dimensions in this table.
• Rise: The minimum nonwetting height above the steam outlet of the SDU-E.
• Spread: The minimum nonwetting width from the steam outlet of the SDU-E.
Throw: The minimum nonwetting horizontal distance from the steam outlet of the SDU-E.
mc_042710_1300
Dispersion: SDU
mc_042710_1435