Specifications
DRI-STEEM Vapormist humidifier • Page 17
mc_042710_1410
Dispersion: Rapid-sorb
Note:
The above data apply to all air velocities up to 1,500 fpm (7.6 m/s) and are based on air leaving the zone of humidification at 55 °F (13 °C) and the stated % RH.
Figure 17-1:
Rapid-sorb non-wetting distances
Table 17-1:
Rapid-sorb dispersion tube capacities*
Tube capacity Tube diameter
lbs/hr kg/h inches DN
d35 d16 1½ 40
36-70 17-32 2 50
* If duct height is <15" (381 mm), tube quantities may need to increase to compensate
for reduced capacity of short tubes. Consult DRI-STEEM or see Dri-calc for the correct
calculation.
Table 17-2:
Rapid-sorb header capacities
Header capacity Header diameter
lbs/hr kg/h inches DN
d250 d113 2 50
251-500 114-227 3 80
501-800 228-363 4 100
0 10203040506070 8090
40
50
60
70
80
90
ENTERING % RH
LEAVING % RH
0
DISPERSION TUBE SPACING
6” 24”18”12”9”