Specifications

1BHFt%3*45&&.)VNJEJUFDI&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBM
$BQBDJUJFTFMFDUSJDBMTQFDJGJDBUJPOT
BOEXFJHIUT
Overview
Figure 4-1:
Steam outlet connections
DC-1168
Hose clamp (for vapor hose)
Table 4-2:
Steam connection sizes
HT model Steam outlet
2, 4, 6, 8
1 ½" hose or
BSP connection
10*, 12*, 14*, 16*
1 ½" or 2" hose or
BSP connection
21, 25, 30, 34
2" hose or
BSP connection
* If using with an SDU-E (Space Dispersion Unit
External Absorption), the Humidi-tech steam outlet
must be 2" to match the SDU-E steam inlet.
The steam outlet is designed to connect to a
vapor hose or BSP connection.
Tap/softened water Humidi-tech shown.
Table 4-1:
Humidi-tech electrical specifications, capacities and weights
HT model Single-phase 230V Three-phase 400V
Shipping
weight (kg)
Operating
weight (kg)
kW Steam capacity (kg/h)
I max. (A) Steam capacity (kg/h) I max. (A)
2 2.5 8.0 37 44
4 5.0 16.0 5.4 8.7* 37 44
6 7.5 24.0 8.2 13.0* 41 56
8 10.0 31.9 10.9 17.3* 41 56
10 12.5 39.9 13.6 15.2* 43 64
12 15.0 47.9 16.3 17.3 43 64
14 19.1 20.2 43 64
16 21.8 23.1** 43 64
21 28.6 30.3** 44 70
25 34.0 36.1** 44 70
30 40.8 43.3** 47 72
34 46.3 49.1** 47 72
*
For wire sizing, the highest leg draw is shown due to current imbalance.
** No available SDU option for these models.
Notes:
t4%6*JTBWBJMBCMFGPS.PEFMT)5UISPVHI)5
t4%6&JTBWBJMBCMFGPSBMMNPEFMTFYDFQU.PEFM)5BOE.PEFMT)5UISPVHI)5
t.PEFMTXJUIUIF4%6PQUJPOIBWFBEEJUJPOBMFMFDUSPOJDDPNQPOFOUTJOUIF)VNJEJUFDIDBCJOFU*GBEEJOHBO4%6BEEUIFGPMMPXJOHUPUIF)VNJEJUFDITIJQQJOH
and operating weights:
SDU-E: 5.5 kg
SDU-I: 4.0 kg
t"MM)VNJEJUFDIIVNJEJmFSTPQFSBUFBU)[
t4%6TTIJQTFQBSBUFGSPNUIF)VNJEJUFDI