Specifications
1BHFt%3*45&&.)VNJEJUFDI&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBM
Bracket under evaporating chamber
allows easy removal for cleaning
Removable
evaporating
chamber
Water fill
access hole
Incoloy alloy-sheathed
immersion heaters
Keyholes
for wall
mounting
Water fill
Electrical area
Skimmer port
and overflow
drain
Electrical conduit knockouts
Flexible vapor hose,
pipe, or tubing
connects to dispersion
tube(s) or to an SDU
Duct
Single
dispersion
tube with
condensate
return line
Figure 2-3:
Installation overview
(Humidi-tech for tap/softened water shown)
1SPEVDUPWFSWJFX
OM-82-4
Notes:
See Pages 8 and 9 for detailed installation
drawings.
Damage caused by chloride corrosion is not
covered by your DRI-STEEM warranty.
Overview
Figure 2-2:
Water level control for DI/RO water
option humidifier
Supply water connection
Float rod
Float ball
OM-7396
Humidifiers using tap or softened water
control water levels electronically using a
three-rod probe. The controller responds
with the above actions when the water level
reaches each rod.
Figure 2-1:
Water level control for tap/softened
water humidifier
VLC-OM-030
Fill valve opens when water
level is below this probe.
Low-water cutoff. Power to
heaters is cut if water level
drops below this probe.
Fill valve closes when water
level rises to this probe.
Humidifiers using DI/RO water control water
levels using a float valve and low-water
cutoff switch.
Tap/softened water
Humidi-tech humidifiers with tap/softened water (shown above)
use electricity to heat tap or softened fill water into steam for
humidification. A conductivity probe monitors the water level;
therefore, water conductivity must be at least 30 μS/cm for proper
operation. Humidi-tech with tap/softened water will not operate
with DI/RO water. For DI/RO water, use Humidi-tech with the
DI/RO water option.
DI/RO water option
Humidi-tech humidifiers with DI/RO water systems (systems using
deionized water or water that has been treated using reverse osmosis)
use electricity to heat DI/RO fill water into steam for humidification.
Water level is controlled with a float valve and low water cutoff
switch. Float valves are compatible with DI/RO water only.
Humidifiers with the DI/RO water option are virtually maintenance
free and require little or no downtime.
Water type conversion
Humidi-tech tap/softened water humidifiers can be converted in
the field for use with DI/RO water, and Humidi-tech DI/RO water
humidifiers can be converted in the field for use with tap/softened
water. Contact your DRI-STEEM representative or distributor for
parts and instructions.