Figure 36-1:
Cover enclosure screw cap detail
OM-778-3
Humidifier De-scaling Solution
Scale buildup on humidifier heaters acts as an
insulator, reducing humidifier performance while
increasing energy costs. To keep humidifiers
operating as efficiently as possible, remove scale
with DRI-STEEM's Humidifier De-scaling Solution,
available for purchase from your DRI-STEEM
representative or distributor.
The De-scaling Solution cleans without risk
of corroding humidifier tanks or welds. The
De-scaling Solution also cleans surfaces
unreachable by hand scraping.
DRI-STEEM's Humidifier De-scaling Solution is
the only approved cleaner/de-scaler for use with
DRI-STEEM humidifiers. Use of other cleaners/
de-scalers may void your DRI-STEEM warranty.
5BQTPGUFOFEXBUFS
Maintenance
Inspection and maintenance
 "OOVBMMZ (also recommended when maintenance is performed)
t *OTQFDUUBOLBOEHBTLFUTGPSMFBLT
t .FBTVSFDVSSFOUESBXPGIFBUFSTBOEWFSJGZBNQWBMVFTQFS
stage by comparing to the wiring diagram located inside the
subpanel cover. This identifies any burned out heaters. Only
qualified electrical personnel should perform this task.
t "MMTBGFUZEFWJDFTJOUIFDPOUSPMDJSDVJUTIPVMECFDZDMFEPO
and off to verify they are functioning. These include:
High limit switch
Airflow proving switch
Low water level probe. Pull out probe plug; fill valve
should energize.
Cool down humidifier
Before performing any maintenance, allow the tank to cool down.
Fresh make-up water is used to speed up cooling. Do not close the
manual water supply before cooling down the humidifier; otherwise
the tank could stay hot for several hours.
t *OTVMBUFEBOEVOJOTVMBUFEUBOLTXJMMIBWFIPUTVSGBDFT
t 7FSJGZUIBUUIFSFJTOPDBMMGPSIVNJEJUZBOEUIBUUIFBRVBTUBUTFU
point (adjusted using the keypad/display Setup screens) is less
UIBOSPPNUFNQFSBUVSFEFGBVMUTFUUJOHJT¡'<¡$>TPUIBU
the heaters do not energize while cooling down the tank.
t .PEFMTXJUIBTUBOEBSEESBJOWBMWF
Manually open the drain valve by moving the valve lever
located on the back of the drain valve to the manual open
position. The fill valve eventually opens.
Let the fill water run until the tank is cooled, then shut off
the field-installed manual supply water shut-off valve.
Let the tank drain, then manually close the drain valve.
t .PEFMTXJUIPQUJPOBMESBJOWBMWFT
For drain valves without the manual open lever, use the
keypad to perform the cool down process.
Go to the control modes screen and select Manual Drain.
Allow approximately half the water to drain out of the tank.
In the Control Modes screen select Auto; the fill valve opens
and the humidifier cools down.
When the fill valve closes, select Manual Drain in the
Control Modes screen and let the tank drain dry. The
humidifier should be cool enough to work on.
For more information about using the keypad, see the
Vapor-logic4 Installation and Operation Manual.