Specifications

%3*45&&.)VNJEJUFDI&MFDUSJD)VNJEJGJFS*OTUBMMBUJPO0QFSBUJPOBOE.BJOUFOBODF.BOVBMt1BHF
%JTQFSTJPO
3BQJETPSC
Installation
4. Mount the dispersion tubes on the header with the slip
couplings or hose cuffs:
t 8IFOJOTUBMMJOHTMJQDPVQMJOHTGPS%/EJTQFSTJPOUVCFT
take care not to shear O-rings.
t 4FUTMJQDPVQMJOHPOIFBEFSTUVCPSEJTQFSTJPOUVCFTP0SJOH
is resting on face of tubing.
t 3PUBUFTMJQDPVQMJOHXIJMFQVTIJOHJUPOUPUIFUVCJOH
t 0SJOHTBSFMVCSJDBUFEBUGBDUPSZ*GBEEJUJPOBMMVCSJDBUJPOJT
necessary, DO NOT use petroleum-based lubricant.
5. Allow the dispersion tubes to rest against the bottom of the duct.
6. Position the flange of the L-bracket so it is upstream of the tubes
when the assembly is rotated into position. Fasten the L-bracket
to the end of the dispersion tubes with the provided bolt, lock
washer, and flat washer.
7. Rotate the assembly up until the L-bracket aligns with the
mounting holes in the duct or air handler.
t %/EJTQFSTJPOUVCFT
Header pitch is duplicated in the L-bracket.
Dispersion tube and slip coupling must be fully engaged
on header stub for O-rings to provide a seal.
High end of L-bracket can be fastened tight to duct or
air handler.
Fastener on low end of L-bracket must be long enough
to compensate for pitch. Use a nut on both sides of
L-bracket and duct or air handler for stability.
t %/EJTQFSTJPOUVCFT
Fasten bracket to top of duct and use hose cuffs to
compensate for header pitch.
Before securing hose cuffs with hose clamps on
dispersion tube and header stub, verify that dispersion
tube orifices are directed perpendicular to airflow.
8. Verify that all fasteners are secure:
t -CSBDLFUUPEVDU
t %JTQFSTJPOUVCFTUP-CSBDLFU
t )PTFDMBNQTPO%/UVCFT
t )FBEFSTVQQPSUCSBDLFUGBTUFOFS
9. Secure and seal the header escutcheon plate around the header.
Note:
See Page 32 for steam supply and condensate
drain line connection instructions.