Table 27-1:
Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units
Airflow
Type of
interconnecting piping
Diameter of
interconnecting piping
Pitch of
interconnecting piping
Pitch of
dispersion tubes
Pitch of
header
Horizontal
Vapor hose
DN40
DN50
15%
toward Rapid-sorb
Vertically
plumb
1%
toward condensate
drain
Tubing or pipe
DN40
DN50
1%
toward Rapid-sorb
Vertical
Vapor hose
DN40
DN50
15%
toward Rapid-sorb
15%
toward header
1%
toward condensate
drain
Tubing or pipe
DN40
DN50
1%
toward Rapid-sorb
%JTQFSTJPO
3BQJETPSC
Installation
Table 27-2:
Rapid-sorb dispersion tube capacities
Tube capacity Tube diameter
kg/h DN
≤ 16 40
17-32 50
Table 27-3:
Rapid-sorb header capacities
Header capacity Header diameter
kg/h DN
≤ 113 50
114-227 80
228-363 100
364-591 125
592-955 150
Pitch requirements
t 'PS3BQJETPSCXJUIUIFIFBEFSPVUTJEFB
horizontal-airflow duct, consider the following:
– DN40 dispersion tubes: Use a fastener of sufficient length to
accommodate the 1% pitch requirements toward the DN20
header drain fitting.
– DN50 dispersion tubes: The bracket can be mounted flush to
the ductwork. The 1% pitch typically can be accomplished in
the length of the hose cuffs used to connect the tubes to the
header.
t 4FF5BCMFBOEUIFESBXJOHTPOUIFGPMMPXJOHQBHFTGPS
pitch requirements.